Menus

Main Menu

Current operating mode

Information only. This is changed in the menu "Settings"

Water and Mains startup

This section is NOT about the Dump Load regulation. Dump Load regulation is always active.

If you have electrical water valves and/or a mains contactor, and you have set the valves NOT to open automatically on power up, then you can open the valves here.

Settings

as the name says

Status Menu

Only for looking. No settings possible - except you can reset the controller in this menu

Warnings

Look at warnings. With warnings, the hydrocontrol still regulates.

Show errors and shut of cause

With errors, the hydrocontrol sets the dump loads to 100% and tries to shut the system down. It won't recover automatically. You have to enter the menu and reset the error.

Status

Possible modes: Normal Operation, Warnings, Error.

Regulating, or dump loads 100%

Settings

Operating Mode

Electronic Load Controller

The controller tries to keep the frequency stable. Suitable for synchronous generators.

Induction Generator Controller

The controller tries to keep the voltage stable. Suitable for asynchronous (induction) generators.

Automatic Load control

The controller DOES NOT regulate frequency or voltage. It switches on/off user loads, if there is enough power available, or if there is too little power. E.g. water pumps, heaters.

Output test

Test the outputs directly. This is to verify you have wired everything correctly, of for trouble shooting

3 phases

Single phase operation or 3 phase operation.

3 phase operation will...

- adapt the timing (triggering angles) of the triacs for line 2 and line 3 phase angle switching.

- it will also monitor line 2 and line 3 voltages

Common reference point for zero crossings and voltages.

If your system has neutral, then use the default.

If your system does not have neutral, then Line 1 will be the common reference.

If you have Line 1 as common reference, then use this wiring for Mains connector on PCB

Variable dump load wiring

(only relevant for 3 phase operation)

Star

(also called Y), connected to neutral. Default setting

Delta, between lines

If you have Neutral as reference, but the dump loads are connected as delta, then this setting adapts the triggering angles.

Regulation

Set points

Total turbine capacity

This setting is currently not used. In the future, it could be used to do plausibility checks, and warn you if the water intake is blocked, or if water is low, or to set the position of a spear valve with MPPT.

ELC only: target frequency

Even in IGC mode, this setting is monitored, and the system will go into error mode if the thresholds specified in the "warnings, protection" menu are exceeded.

IGC only: target voltage RMS

Even in ELC mode, this setting is monitored, and the system will go into error mode if the thresholds specified in the "warnings, protection" menu are crossed.

Tolerated deviation from set point

If your dumploads have different sizes, and as a result the system constantly "hunts" by switching dumploads on and off, you can specify a "corridor" here, where a deviation from the set point is acceptable, and where dump loads will not be switched.

E.g. if you allow a tolerance of 1%, then the ELC will only start switching dumploads, once the freqeuncy crosses 49.5 Hz or 50.5. Hz.

Droop (setpoint shifts with load)

This might be useful if you have 2 generators, which should balance the load among each other.

IGC

Input control value - Peak voltage or RMS voltage.

If your generator does not produce sine waves, then using RMS (root mean square, the average of the wave form) as input might lead to high peak voltages.

Using peak voltage (the highest point of the waveform) as input, the peaks can be prevented.

Regardless of this setting, the set point is always entered as RMS value.

Water valves

Electric water valves - Yes or NO

If YES, then the hydrocontrol does the needed calculations. Assign the corresponding functions in the Menu Output > Relays

If NO, then the corresponding functions will not work.

Threshold

If dump loads ON are less than xx%, then open valves (shortage of energy)

If dump loads OFF are less than xx%, then close valves (too much energy)

Water valve type

variable flow

If you water valve(s) can regulate the water continuously (spear valve or suitable butterfly valve), then use this

Fixed flow

If your water valves can only be totally closed or totally open (you need more than one valve in this case) - e.g. butterfly valves, which are not designed for continuous operation - then you can open or close one valve after the other.

Fixed flow only: Seconds before operating the next valve.

The system might need many seconds to stabilize, after a valve has been opened/closed. Here you can delay the operation, so the same valve does not open immediately again, or the next valve closes too fast.

Water valve duty cycle

(only makes sense for variable flow)

If you valve motor operates very fast, it might help to operate it only a few seconds at a time, and let the system stabilize after each correction

To be implemented: MPPT

If the problem is too little water, closing the spear valve will increase power output. A MPPT (maximum power point tracking) algorithm will be used to find the optimum valve position.

P-I setup

Adaptive control

Not implemented at the moment. You will have to manually find the best P- and I-value

3 phase load balancing

Software not implemented at the moment. The hardware is ready.

Main Input Valve timer

If your MIV motor has no end position switches, you can turn off the current to the motor after a specified time.

Invert <close water valve> relay function

If the hydrocontrol fails for whatever reason, then the <valve close> relay falls into the <close> position, and the valve motor will get power from the 12V battery indefinitely. This is a safety feature which ensures that in case of hydrocontrol failure, the water will be shut off.

The disadvantage is that the valve motor might be destroyed. By inverting the function, there won't be an automatic water shutoff in case of hydrocontrol failure, but the motor will stay safe.

Water and mains startup

This menu has NO effect on dump load regulation. Dump load regulation is always active.

Open water valve manually or automatically

If the hydrocontrol has a secondary permanent power supply from 12V battery, you can open the water valve with the START button.

If there is no secondary power supply, you can use the START button to hand over valve control to the hydrocontrol.

Use "automatic" to start up the hydro power system without needing access to the hydrocontrol keyboard and screen.

Mains user contactor.

If this contactor is closed automatically as soon as nominal frequency is reached, power might break down.

Here you can delay the connection of the users, until the system has built up a reserve.

Protection, Warnings

Protection functions

These are the absolute limits. If exceeded, the system will go into error mode and set dumploads to 100% permanently.

The warning thresholds are calculated automatically by the hydrocontrol at 50% of the error thresholds.

Overvoltage

These are the absolute limits. If exceeded, the system will go into error mode and set dumploads to 100% permanently.

The warning thresholds are calculated automatically by the hydrocontrol at 50% of the error thresholds.

Warning alerts, notifications

You can decide which kind of warning triggers the Warning relay, the Hum signal (see below) and the SMS (option)

Hum Signal Sound

You can alert all users that something is wrong with the system. This is especially useful if the system is overloaded.

The users will now have to disconnect some loads.

The hydrocontrol will regularly switch on some dump loads. The resulting frequency drop will change the sound of the hum in user appliances. If they hear this, the should switch off loads.

Fault checks

Dump load check

This feature is disabled at the moment, because it produced problems with dump load switching in some systems. A new approach is tested and in progress at the moment.

Fan check

If your hydrocontrol has fans to force-cool the heat sinks, then the function of the fans (the current through the motor) is monitored.

Mobile Communication

Input calibration

Volts

Ampere

AC noise reduction

Temperature limits

Outputs

Dump loads

Switching type

SSRs

Relays

High priority auxiliary Loads

Test

Auto user Load mode

Password

SD card

Status menu

Input readings

Temperatures

Output status

regulation response

live graph

microcontroller

ethernet

System capacity

P-I