Đồng hồ đo đa năng

Đồng hồ đo đa năng

1.kyoritsu 6016
THÔNG SỐ KỸ THUẬT:

+ Chỉ thị số
+ Đo thông mạch, đo mạch vòng, đo điện trở đất...
+ Phạm vi đo: 20/200/2000MΩ /: 20/200MΩ ;  250/500/1000V  DC
Bảo hành : 12 tháng
Hãng sản xuất : Kyoritsu - Nhật
Xuất xứ : Nhật

Continuity Measurement
Continuous testing can be carried out by use of the test button lockdown feature. A selectable buzzer gives instantaneous indication of continuity. Null facility eliminates the test lead resistance from the results, the nulled value is retained even if the instrument is switched off. Live circuit warnings are given by a flashing LED, buzzer and indication on the display.
Insulation Measurement
Three selectable test voltages 250V, 500V and 1000V. An auto-discharge function ensures that circuits are not hazardous after testing. A red LED gives warning of high voltage output during testing and discharging of the circuit. In case of connecting to a live circuit, a live circuit warning is given by flashing LED, buzzer and indication on the display.
Loop Impedance Measurement
A patented (ATT) low current loop impedance test enables high accuracy loop measurements and quick testing without tripping RCD's.
A high current alternative is selectable for even higher accuracy and instantaneous results. The subsequent test will default to the low current test, this saves any inadvertent tripping of the RCD. The KEW 6016 allows also for phase to phase loop tests.
6016
CE
10 in 1
PSC / PFC Measurement
The Prospective Short Circuit Current (PSC) and Prospective Fault Current (PFC) are automatically calculated and shown on the display. As loop testing, the function has low and high test current options with the default to low current to avoid inadvertent tripping of RCDs.
RCD Measurement
The KEW 6016 has a comprehensive RCD test feature for RCD type AC (Alternative Currents), RCD type A (Pulsating Direct Currents), General and Selective (delayed).
Measures at 1/2x, 1x, 5x of nominal RCD current. It also has Ramp Test and Auto test where all results are shown on one screen. Touch voltage limit can be selected for 25V or 50V depending on application.
Earth Measurement
Using the classical Volt-Amper method with two auxiliary earth spikes and without external power source. All test leads and spikes are supplied as standard accessories.
Phase rotation
KEW 6016 can check the phase rotation of three phase lines with clear indication of the sequence on the display.
Voltage Measurement
In addiction to the voltage measurement, this function gives also the Frequency of the voltage under test.

NEW
Continuity
Range|20/200/2000Ω (Auto-ranging)
Open circuit voltage (DC)|5V±20% (*1)
Short circuit current|Greater than 200mA
Accuracy|±0.1Ω (0~0.19Ω)
|±2%rdg+8dgt (0.2~2000Ω)
Insulation Resistance
Range|20/200MΩ
|(Auto-ranging)
|20/200/2000MΩ (Auto-ranging)
Open circuit voltage (DC)|250V+25% -0%|500V+25% -0%|1000V+20% -0%
Rated current|1mA or greater
|@ 250kΩ
|1mA or greater
|@ 500kΩ
|1mA or greater
|@ 1MΩ
Accuracy|±2%rdg+6dgt (0~19.99MΩ)
|±5%rdg+6dgt (20~200MΩ)
|±2%rdg+6dgt (0~199.9MΩ)
|±5%rdg+6dgt (200~2000MΩ)
Loop Impedance
Function|L-PE|L-PE (ATT)|L-N / L-L
Rated Voltage|100~260V 50/60Hz|L-N: 100~300V
|L-L: 300~500V 50/60Hz
Nominal Test Current at 0Ω External Loop: Magnitude / Duration (*2)|20Ω: 6A/20ms
|200Ω: 2A/20ms
|2000Ω: 15mA/500ms
|L-N: 6A/60ms
|N-PE: 10mA/approx. 5s
|20Ω: 6A/20ms
Range|20/200/2000Ω
|(Auto-ranging)
|20/200/2000Ω
|(Auto-ranging)
|(L-N < 20Ω)
|20Ω
Accuracy|±3%rdg+4dgt (*3)
|±3%rdg+8dgt (*4)
|±3%rdg+6dgt (*3)
|±3%rdg+8dgt (*4)
|±3%rdg+4dgt (*3)
|±3%rdg+8dgt (*4)
PSC (L-N / L-L) / PFC (L-PE)
Function|PSC|PFC|PFC (ATT)
Rated Voltage|100~500V 50/60Hz|100~260V 50/60Hz|
Nominal Test Current at 0Ω External Loop: Magnitude / Duration (*5)|6A/20ms|6A/20ms
|2A/20ms
|15mA/500ms
|L-N: 6A/60ms
|N-PE: 10mA/approx. 5s
Range|2000A/20kA Auto-Ranging
Accuracy|PSC / PFC accuracy is derived from measured loop impedance
|specification and measured voltage specification
RCD
Function|X1/2|X1|X5|Ramp|Auto
Trip current setting|10/30/100/300/
|500/1000mA
|10/30/
|100mA
|10/30/
|100/300/
|500mA
|Depending on the
|accuracy at each
|function.
|Measurement sequence:
|X1/2 0°→X1/2 180°
|→X1 0°→X1 180°
|→X5 0°→X5 180°
|Measurements with
|x5 are not carried out
|for RCDs with
|nominal current of
|100mA or more.
Trip current Duration|2000ms|G: 550ms
|S: 1000ms
|410ms|Goes up by
|10% from 20% to
|110%
|G:300ms/
|S:500ms
|X10 times
Rated Voltage|230V+10%-15% 50/60Hz
Accuracy|AC Type:
|-8%~-2%
|A Type:
|-10%~0%
|AC Type: +2%~+8%
|A Type: 0%~+10%
|AC Type: ±4%
|A Type: ±10%
|Trip time: ±1%rdg+3dgt
RCD (Uc)
Function|UC
Rated Voltage|230V+10%~15% 50/60Hz
Range|100.0V
Test current|≤ 1/2IΔn (max150mA)
Accuracy|+5%~+15%rdg, ±8dgt
Earth
Range|20/200/2000Ω Auto-Ranging
Accuracy|20Ω: ±3%rdg+0.1Ω
|200/2000Ω: ±3%rdg+3dgt (Auxiliary earth resistance 100±5%)
Phase Rotation
Rated voltage|50-500V 50/60Hz
Remarks|Correct phase sequence: are displayed "1.2.3" and recycle mark
|Reversed phase sequence: are displayed "3.2.1" and recycle mark
Volts
Function|Volts|Frequency
Rated voltage|25~500V, 45~65Hz
Measuring range|25~500V|45~65Hz
Accuracy|±2%rdg+4dgt|±0.5%rdg+2dgt
General
Applicable standards|IEC 61010-1 CAT.III 300V (500V L to L) Pollution degree 2, IEC 61010-031,
|IEC 61557-1, 2, 3, 4, 5, 6, 7, 10, IEC 60529 (IP40), IEC 61326 (EMC)
Power source|LR6 X 8
Dimensions|136(L) X 235(W) X 114(D)mm
Weight|1350g (including batteries.)
Accessories|7188A (Distribution board fuse test lead set)
|7196A (Test leads with remote control switch)
|7218A (Power cord [EU]) (*6)
|7228A (Earth resistance test leads)
|8032 (Auxiliary earth spikes)
|8212-USB (USB adaptor with KEW Report (Software))
|9142 (Carrying case)
|9121 (Shoulder strap)
|Cord case, Buckle, Battery, Instruction manual
Optional|8212-RS232C (RS232C adaptor with KEW Report (Software))
(*1):Voltages are output when measurement resistance is under 2100 ohm.
(*2):at 230V
(*3):230V+10%-15%
(*4):voltages except for (*3)
(*5):at 230V
(*6):7187A (Power cord [UK]), 7221A (Power cord [SA]), 7222A (Power cord [AU])

2. kyoritsu 6010 A
THÔNG SỐ KỸ THUẬT:

+ Chỉ thị số
+ Đo thông mạch, đo mạch vòng, đo điện trở đất...
+ Phạm vi đo: 20/2000Ω ;   25A(20Ω  range)  
                         15mA(2000Ω range) ;  500V DC-570V  DC
Bảo hành : 12 tháng
Hãng sản xuất : Kyoritsu - Nhật
Xuất xứ : Nhật

 
Continuity and Insulation Testing
Live circuit warning LED:
Immediate illumination of a warning lamp if the circuit under test is live
Auto Discharge:
Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
Integral overload protection on internal continuity and insulation test circuitry
Autoranging
500V DC test voltage for insulation tests
200mA short circuit current on continuity ranges
  
6010A
CE
Loop and RCD Testing
Wiring connection check LED’s:
Immediate indication if wiring of circuit under test is correct
Overheat Protection:
Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
Supply Voltage Indication:
Can display supply voltage value in loop impedance mode
Low Current Loop Impedance Test:
Short duration low test current will prevent tripping of many passive RCDs
Auto Data Hold:
Retains displayed reading for set period following test
Phase Angle Selection:
Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs
 
Continuity Testing
Measuring Ranges0~19.99 and 10.0~199.9Ω (2 auto ranges)
Open Circuit Voltage> 4V (as per IEC 364)
Short Circuit Current> 200mA DC (as per IEC 364)
Accuracy|±(3% + 3dgt)
Loop Impedance Testing
Rated Voltage230V AC +10%-15% (50Hz)
Voltage Measuring Range100-250V AC (50Hz)
Impedance Range
Nominal Test Current
20/2000Ω
25A (20Ω range) 15mA (2000Ω range)
Test Period1/2 cycle (10ms)
Accuracy20Ω range : ±(3% + 8dgt)   2000Ω range : ±(3% + 8dgt)
Insulation Testing
Measuring Ranges0~19.99 and 10.0~199.9MΩ (2 auto ranges)
Test Voltage500V DC
Output Voltage on
Open Circuit
570V DC±6%
Rated Current> 1mA (as per IEC 364)
Accuracy|± (3% + 3dgt)
RCD Testing
Rated Voltage230V AC +10%-15% (50Hz)
Trip Current SettingsRCD × 1/2: 5, 15, 50, 150, 250mA
RCD × 1: 10, 30, 100, 300, 500mA
Trip Current DurationRCD × 1/2 × 1: 2000ms
Fast Trip150mA
AccuracyTrip current ±3% of test current at 230V. 
Trip time ±(3% + 3dgt)
General
Safety StandardIEC 61010-1 CAT.III 300V Pollution Degree 2
IEC 61010-2-031
IEC 61557
Withstand Voltage4000V AC for 1 minute
Power SourceR6P (AA) (1.5V) × 8
Dimensions175(L) × 115(W) × 86(D)mm
Weight780g approx.
Accessories7122B (Test leads) 
KAMP10
* (Test Lead with IEC Connector)
Pouch for Test leads
Shoulder Strap
Shoulder Pad
R6P (AA) × 8
Instruction Manual
Optional7133B (Distribution board test leads)
*KAMP10(EU): European SHUKO plug
KAMP10(UK): British plug(13A)
KAMP10(AU): Australian plug
KAMP10(SA): South African plug



3. kyoritsu 6050

THÔNG SỐ KỸ THUẬT:

+ Chỉ thị số
+ Đo thông mạch, đo mạch vòng, đo điện trở đất...
+ Thông số : 20/200/2000Ω   ;     (LOOP 200/2000Ω, PSC 200A:100 ~ 440V)
Bảo hành : 12 tháng
Hãng sản xuất : Kyoritsu - Nhật
Xuất xứ : Nhật


6050
Kew Combitester provides the ultimate in Microprocessor technology offering Loop and RCD tests with a comprehensive memory and downloading test results.
LOOP Impedance 200/2000Ω range measurement is carried out using a test current of 15mA. This current will not trip RCD’s rated at 30mA or greater.
High resolution for low Loop Impedance (resolution of 0.01Ω) on 20Ω range.
Direct reading of Prospective Short Circuit Current (PSC) and earth fault current.
RCD tests at 0 and 180 degree phase angle switch permit quick tests and consistent readings.
Test of a large kind of RCD's:
Standard, Selective, AC and A (DC sensitive breakers).
Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings.
RCD Ramp test in order to indicate the actual tripping current of RCD.
Contact Voltage Reading (UC). with two selectable contact voltage limits (50 and 25V).
Visual indication of correct wiring status and automatic lock-out if test resistors overheats.
Designed to IEC 61010-1, IEC 61557 and high protection degree IP54.
The stored data can be transferred to PC via Optical Adapter Model 8212-RS232C and 8212-USB.

CÔNG TY TNHH TRUNG AN

Địa Chỉ: 124/46 Phan Huy Ích , P. 15, Q. Tân Bình, Tp. HCM

Tel : (08) 38150410 - Fax: (08) 38150410

Hotline: 091 7080310 (Mr. Trung)-0909.67.4225 (Mr.Tín)-097 8057811 (Ms. Trinh)

Email: trungankd@gmail.com

Website: https://www.sites.google.com/site/congtytnhhtrungan/

https://www.facebook.com/congtytnhhtrungan

STK: 102010002108889 Ngân Hàng Vietinbank Chi Nhánh TP.HCM

Comments